Bearing on masonry (Georgia R502.6)

Georgia amends IRC R502.6 (Georgia DCA amendments to the 2018 IRC), which governs how the ends of joists, beams and girders are supported.

Minimum bearing lengths

  • On wood or metal: not less than 1-1/2 in (38 mm).
  • On masonry or concrete: not less than 3 in (76 mm).

The trap is using the 1-1/2 in wood or metal figure on masonry. A floor joist on a masonry wall needs 3 in. The 2 in figure is the sill plate thickness, not a bearing length, and 1 in has no basis in the section.

Direct bearing or a 2 in sill plate

On masonry or concrete, bearing is direct, or a sill plate of 2 in minimum (51 mm) nominal thickness is provided. A girder on a CMU pier bears directly on the masonry or on a sill plate at least 2 in nominal. A 1 in nominal plate is too thin, and a fiber expansion strip is not mentioned.

Other permitted supports

  • Approved joist hangers.
  • For joist ends, a 1x4 ribbon strip nailed to the adjacent stud.

The ribbon strip supports joist ends at studs. It is not a bearing surface on masonry.

Mixed supports

Check each end against its own support. A beam on a steel ledger at one end and a brick pier at the other needs 1-1/2 in on the steel and 3 in on the brick. The traps: 1-1/2 in at both ends puts the metal figure on masonry, 3 in at both ends overstates the metal requirement, and 3 in on steel with 1-1/2 in on brick swaps them.

Spotting the one that fails

  • 3 in of direct bearing on a concrete foundation wall: permitted.
  • Approved joist hangers: permitted.
  • A 1x4 ribbon strip nailed to the adjacent stud at joist ends: permitted.
  • 1-1/2 in directly on a brick wall: not permitted, because masonry needs 3 in.

Knowledge check

4 questions on what you just read. Each answer shows the full explanation and its source.