Joist bearing and concrete cover

Joist bearing under Georgia's R502.6

The Georgia DCA amendment to IRC R502.6 (effective January 1, 2020) requires the ends of each joist, beam or girder to have:

  • not less than 3 in (76 mm) of bearing on masonry or concrete;
  • not less than 1½ in (38 mm) of bearing on wood or metal.

The listed common error is applying the 1½ in wood or metal figure to concrete. There is no 4 in figure in R502.6.

Direct bearing or a 2 in sill

Georgia's change adds a rule on how the member bears on masonry or concrete: the bearing shall be direct, or a sill plate of 2-inch minimum (51 mm) nominal thickness shall be provided.

Traps here:

  • 2 in is the sill plate's nominal thickness, not the bearing length. The bearing length on concrete is 3 in.
  • A 1½ in sill plate mixes up the wood or metal bearing length with the sill thickness.
  • The 1x4 ribbon strip nailed to adjacent studs is an alternative support for joist ends in framed walls, not a way to bear on concrete. Approved joist hangers are the other alternative.
  • The amendment does not call for a steel bearing plate.

Concrete cover against earth

Concrete cast against and permanently in contact with earth, such as a footing, needs 3 in (76 mm) of specified cover over the reinforcement. ACI 318-19 Table 20.5.1.3.1 states this. The 2 in and ¾ in figures fall short of it, and 1½ in is a Georgia R502.6 bearing length, not a cover figure.

Which edition, which table

The 2018 IBC references ACI 318-14, and the table numbers differ between editions:

  • ACI 318-14: specified cover is in Section 20.6.1, general requirements at 20.6.1.3, including Table 20.6.1.3.1.
  • ACI 318-19: the cover table is Table 20.5.1.3.1.

The listed common error is citing the 318-19 table number when answering from the 2018 IBC. In 318-14, 25.4.2 is development of deformed bars in tension and 19.3.1 is exposure categories.